If the heating does not work even after checking all of the above checks, do as below.
> If the actuator fails, separate the valve body and the actuator for emergency heating.
> Use a manual valve to turn on/off the heating.
> Request warranty after emergency heating.
-
The boiler heats up even though the set temperature is lowered.
1. Check: Is the actuator and valve loosely assembled?
> Action: Turn the actuator and valve connection clockwise to secure the loosened connection.
-
Even though the thermostat heating indicator mark and the actuator lamp are on, there is no heating.
1. Check: Is there any debris in the pipes?
> Action: Clean the strainer before using it.
2. Check: Is there any AIR pocket in the piping?
> Action: Remove the AIR before using it.
3. Check: In case of individual heating, is the boiler operating normally?
> Action: Ask the boiler manufacturer for after self-testing the boiler.
-
The thermostat heating indicator is on but no heating.
1. Check: Is the thermostat set temperature lower than the room temperature?
> Action: Set the set temperature higher than the room temperature.
2. Check: Is the LED lamp on the actuator at the bottom of the sink on?
> Action: When the thermostat heating icon is on, make sure that the actuator LED lamp in the room is on at the same time.
3. Check: Is there a sound of heating water flowing through the distributor pipe at the bottom of the sink?
> Action: If there is no sound, contact the management office
-
The thermostat LCD screen does not come on.
1. Check: Is the power plug not out?
> Action: Plug in the sink lower motor controller power plug.
2. Checked: Is the thermostat engaged in good?
> Action: If it is not closely attached to the wall, request an aftersales service.